System No. F-C-2191
March 16, 2004
F Rating — 1 Hr
T Rating — 3/4 Hr

1. Floor-Ceiling Assembly
The 1 hr fire-rated wood joist floor-ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Designs in the UL Fire Resistance Directory, as summarized below:A. Flooring System
Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor-Ceiling Design. Max diam of floor opening is 5 in.
B. Wood Joists
Nom 10 in. deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped.
C. Wallboard, Gypsum*
Nom 5/8 in. thick as specified in the individual Floor-Ceiling Design. Wallboard secured to joists as specified in the individual Floor-Ceiling Design.
2. Chase Wall
The through penetrant (Item 3) shall be routed through a 1 hr fire-rated single, double or staggered wood stud/gypsum wallboard chase wall constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:A. Studs
Nom 2 by 8 in. lumber or double nom 2 by 4 in. lumber studs.
B. Sole Plate
Nom 2 by 8 in. lumber or parallel 2 by 4 in. lumber plates, tightly butted.
C. Top Plate
The double top plate shall consist of two nom 2 by 8 in. lumber plates or two sets of nom 2 by 4 in. lumber plates, tightly butted. Max diam of opening is 5 in.
D. Wallboard, Gypsum*
Thickness, type, number of layers and fasteners shall be as specified in individual Wall and Partition Design.
3. Through Penetrants
One nonmetallic pipe to be installed either concentrically or eccentrically within the firestop system. Diam of the circular opening in flooring, and top and sole plates of chase wall 1/2 in. larger than the actual diam of the pipe such that the annular space is min 0 in. (point contact) to max 1/2 in. Pipe to be rigidly supported on both sides of floor-ceiling assembly. The following types and sizes of nonmetallic pipes may be used:A. Polyvinyl Chloride (PVC) Pipe
Nom 4 in. diam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system.
B. Chlorinated Polyvinyl Chloride (CPVC)
Pipe
Nom 4 in. diam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent)
piping systems.
C. Acrylonitrile Butadiene Styrene (ABS)
Pipe
Nom 4 in. diam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
4. Firestop Systems
The firestop system shall consist of the following:A. Packaging Material
Foam backer rod firmly packed into opening as a permanent form.
Packing material to be recessed from top surface of subfloor and bottom surface of lower top plate as required to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* —
Caulk
Min 1/4 in. thickness of fill material applied within annulus, flush with top surface of subfloor or sole plate. At point contact location, a min 1/4 in. diam bead of fill material shall be applied to the penetrant/plywood interface on top surface of floor assembly. Min 1/2 in. thickness of fill material applied within annulus flush with bottom surface of lower top plate. At point contact location, a min 1/4 in. diam bead of fill material shall be applied to the penetrant/top plate interface. RECTORSEAL Biostop 500+
*Bearing the UL Classification Mark