System No. F-C-2151
November 29, 1999
F Rating — 1 Hr
T Rating — 1 Hr

1. Floor-Ceiling Assembly
The 1 hr fire-rated wood joist floor-ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Designs in the UL Fire Resistance Directory, as summarized below:A. Flooring System
Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture*
as specified in the individual Floor-Ceiling Design. Max diam of floor opening is 3 in.
B. Wood Joists
Nom 10 in. deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped.
C. Gypsum Board*
Nom 5/8 in. thick as specified in the individual Floor-Ceiling Design.
2. Chase Wall
The through penetrant (Item 3) shall be routed through a 1 hr fire-rated single, double or staggered wood stud/gypsum wallboard chase wall constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:A. Studs
Nom 2 by 6 in. lumber or double nom 2 by 4 in. lumber studs.
B. Sole Plate
Nom 2 by 6 in. lumber or parallel 2 by 4 in. lumber plates tightly butted.
C. Top Plate
The double top plate shall consist of two nom 2 by 6 in. lumber plates or two sets of parallel 2 by 4 in. lumber plates, tightly butted. Diam of opening to be 3 in.
D. Gypsum Board*
Thickness, type, number of layers and fasteners shall be as specified in the individual Wall and Partition Design.
3. Electrical Nonmetallic Tubing (ENT)+
Nom 1 in. diam (or smaller) Electrical Nonmetallic Tubing
installed either concentrically or eccentrically within the firestop system. The annular space shall be min 0 in. (point contact) to max 1-3/4 in. Through-penetrant shall be rigidly supported on both sides of floor assembly. ENT installed in accordance with Article 331 of the National Electrical Code (NFPA No. 70).See Electrical Nonmetallic Tubing
(FKHU) category in the Electrical Construction Material Directory for names of manufacturers.
4. Firestop System
The firestop system shall consist of the following: A. Steel Wire Mesh
Cylindrical sleeve fabricated from No. 8 steel wire mesh and having a min 1 in. lap along the longitudinal seam. Length of steel mesh to be equal to depth of subfloor, joist and double top plates. Steel wire mesh to be formed to fit periphery of through opening.
B. Packing Material
Min 4 pcf mineral wool batt insulation firmly packed into steel wire mesh as a permanent form. Packing material to be recessed from top surface of subfloor and bottom surface of lower top plate as required to accommodate the required thickness of fill material.
C. Fill, Void or Cavity Material* - Caulk
Min 1/4 in. thickness of fill material applied within annulus, flush with top surface of subfloor and min 1/2 in. thickness of fill material applied within the annulus, flush with bottom surface of lower top plate. At point contact location, a min 1/4 in. diam bead of fill material shall be applied to the penetrant/wood interface on both surfaces of the floor assembly RECTORSEAL Biostop 500+ Caulk