System No. F-A-1044
April 03, 2003
F Rating — 2 Hr
T Rating — 1/4 Hr

1. Floor Assembly
The fire rated unprotected concrete and steel floor assembly shall be constructed of the materials and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below:A. Concrete
Min 2-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf)
concrete.
B. Steel Floor and Form Units*
Composite or non-composite max 3 in. deep galv steel fluted units as specified in the individual Floor-Ceiling Design. Max diam of opening is 14 in.
1A. Floor Assembly
As an alternate to the concrete and steel floor assembly above, min 2-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf)
concrete. Max diam of opening is 14 in.
2. Through Penetrants
One metallic penetrant to be installed eccentrically or concentrically within the firestop system. The annular space between pipe and periphery of opening shall be min of 0 in. (point contact) to max 1-1/4 in. Pipe to be rigidly supported on both sides of floor-ceiling assembly. The following types and sizes of metallic pipes, tubing or conduit may be used:A. Steel Pipe
Nom 12 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe
Nom 12 in. diam (or smaller) cast or ductile iron pipe
C. Conduit
Nom 4 in. diam (or smaller) steel electrical metallic tubing.
D. Conduit
Nom 6 in. diam (or smaller) rigid steel conduit.
E. Copper Tubing
Nom 4 in. diam (or smaller) Type L (or heavier) copper tubing.
F. Copper Pipe
Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe.
3. Firestop System
The firestop system shall consist of the following:A. Packing Material
Foam backer rod firmly packed into opening as a permanent form. Packing material to be recessed from the top surface of the floor to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Materials*-Sealant
Min 1/2 in. thickness of sealant applied within annular space, flush with top surface of floor. At the point contact location between pipe and concrete, a min 1/2 in. diam bead of fill material shall be applied at the concrete/pipe interface on the top surface of floor. RECTORSEAL Biostop 500+
*Bearing the UL Classification Mark