System No. C-AJ-8051
January 15, 1999
F Rating — 3 Hr
T Rating — 0 Hr

1. Floor or Wall Assembly
Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete floor or min 5-1/4 in. thick reinforced lightweight or normal weight concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*.
Floor may also be constrcted of any min 6 in. thick UL Classified hollow-core Precast Concrete Units*.
Max diam of opening is 4 in.See Concrete Blocks
(CAZT) and Precast Concrete Units
(CFTV) categories in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants
A max of two pipes, conduits or tubing to be installed within the opening. The space between pipes, conduits or tubing and periphery of opening shall be min 5/8 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:A. Steel Pipe
Nom 3/4 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Conduit
Nom 3/4 in. diam (or smaller) electrical metallic tubing or steel conduit.
C. Copper Tubing
Nom 3/4 in. diam (or smaller) Type L (or heavier) copper tubing.
D. Copper Pipe
Nom 3/4 in. diam (or smaller) regular (or heavier) copper pipe.
3. Tube Insulation — Plastics+
Nom 1/2 in. thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing installed only on one pipe. The annular space between tube insulation and through penetrants (Item 2) shall be 1/2 in. The annular space between the tube insulation and periphery of opening shall be 3/8 in.See Plastics+
(QMFZ2) cateory in the Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used.
4. Firestop System
The firestop system shall consist of the following:A. Packing Material
Min 3-3/4 in. thickness of min 4.5 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall or hollow-core floor as required to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* — Caulk
Min 3/4 in. thickness of fill material applied within the annulus, flush with top surface of solid concrete floor, or with both surfaces of wall or hollow-core floor. RECTORSEAL Biostop 500+ Caulk
+Bearing the UL Recognized Component Mark
*Bearing the UL Classification Marking