System No. C-AJ-2347
December 20, 2001
F Rating — 3 Hr
T Rating — 0 Hr

1. Floor or Wall Assembly
Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete floor or min 5 in. thick reinforced lightweight or normal weight
(100-150 pcf) concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening shall be 6 in. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants
One nonmetallic penetrant centered within the firestop system. The annular space between pipe and periphery of opening shall be nom 3/4 in. Pipe to be rigidly supported on both sides of the floor assembly. The following types and sizes of non-metallic pipe may be used: A. Polyvinyl Chloride (PVC) Pipe
Nom 4 in. diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (process or supply) or vented
(drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC)
Pipe
Nom 4 in. diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems.
C. Acrylonitrile Butadiene Styrene (ABS)
Pipe
Nom 4 in. diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (process or supply)
or vented (drain, waste or vent) piping systems.
3. Firestop System
The details of the firestop system shall be as follows:A. Fill, Void or Cavity Materials* - Wrap Strip
Nom 1/4 in. thick intumescent elastomeric material faced on one side with plastic film, supplied in 2 in. wide strips. Two layers are individually wrapped around the through penetrant with plastic film exposed and and ends butted and held in place with tape or tie wire. Butted ends in successive layers shall be offset. Wrap strip recessed ½
in. from bottom of floor or from the surface of each wall. RECTORSEAL Biostop Wrap Strip
B. Fill, Void or Cavity Materials* - Caulk
Nom ½ in. thickness of fill material applied within the annulus, flush with bottom surface of floor or both surfaces of wall. RECTORSEAL Biostop 500+
*Bearing the UL Classification Mark